Auto recloser (ACR) is recognized by electric utilities throughout the world as an essential device for achieving their prime goal: providing maximum continuity of electric service to their customers simply and economically. Reclosers sense and interrupt fault currents and automatically restore service after momentary outage.
Auto Recloser is an automatic medium voltage electric switch which is designed for use on overhead electricity distribution networks to detect and interrupt momentary faults. It shuts off electric power when trouble occurs, such as a short circuit. Where a household circuit breaker remains shut off until it is manually reset, a recloser automatically tests the electrical line to determine whether the trouble has been removed. And, if the problem was only temporary, the recloser automatically resets itself and restores the electric power.
On high-voltage electric lines, 80 to 90 percent of trouble occurrences are temporary –such as lightning, windblown tree branches or wires, birds, or rodents–and will, by their very nature, remove themselves from the electric line if the power is shut off before permanent damage occurs to the lines.
The recloser senses when trouble occurs and automatically shuts off the power. An instant later (the length of time may be noticeable only as a lightbulb flicker), the recloser turns the power back on, but if the trouble is still present, it shuts it off again. If the trouble is still present after three such tries, the recloser is programmed to consider the problem permanent and it remains off.
Description | POL-ACR12 | POL-ACR24 | POL-ACR40 |
Rated maximum voltage | 12 kV | 24 kV | 40 kV |
Rated basic impulse level, P>P | 85 kV | 145 kV | 185 kV |
Rated basic impulse level, P>E | 75 kV | 125 kV | 170 kV |
Power frequency withstand, Dry | 50 kV | 60 kV | 70 kV |
Power frequency withstand, Wet | 45 kV | 50 kV | 60 kV |
Rated continuous current | 630 A / 1250 A | 630 A / 1250 A | 1200 A |
Rated fault making current | 50 kA | 50 kA / 63 kA | 42 kA |
Rated fault breaking current | 20 kA | 20 kA | 16 kA |
Cable charging current | 20 A / 40 A | 20 A / 40 A | 40 A |
Line charging current | 5 A / 10 A | 5 A / 10 A | 5A |
Rated fault duration time | 3 s | 3 s | 3 s |
Contact resistance, VCB | < 35 µΩ | < 35 µΩ | < 35 µΩ |
Contact resistance,ABI | < 60 µΩ | < 65 µΩ |
|
Network frequency | 50/60 Hz | 50/60 Hz | 50/60 Hz |
Rated operation voltage | 220 VAC | 24/48 VDC | 24 VDC |
Rated power | 40 W | 40 W | 40 W |
Design specification | IEC 62271-111 | IEC 62271-111 | IEC 62271-111 |
Marking specification | IEEE std C37.60 | IEEE std C37.60 | IEEE std C37.60 |
Operation sequence, no charge | 25 ms trip - 50 ms close - 25 ms trip | 25 ms trip - 50 ms close - 25 ms trip | 25 ms trip - 50 ms close - 25 ms trip |
Long lifespan and low maintance
Polipar's reclosers can last up to 10,000 full load operations thanks to their excellent design and magnetic actuators. For twenty-five years, fewer moving parts mean less maintenance.
High dependability
With only one moving part, Polipar ACR created a straightforward, magnetically actuated operating mechanism that could run dependably. Vacuum interrupter technology makes reclosers as reliable and low maintenance as possible while also being environmentally benign.
Optimal Measurement
Reclosers have voltage sensors and a current transformer in each bushing to measure voltage and current.
Microprocessor based controller
More advanced features in protection, monitoring, metering, communication, and recording are offered by the controller, which can also help your power distribution system become more dependable. Easy integration with DNP3 Level 2, Modbus, and IEC 61850 into Ethernet or serial-based communication networks.